2nd hand ex-project..
Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24 V DC, output: 24 V DC/10 A
Dimensions
| Width | 48 mm |
|---|
| Height | 130 mm |
|---|
| Depth | 125 mm |
|---|
| Width with alternative assembly | 122 mm |
|---|
| Height with alternative assembly | 130 mm |
|---|
| Depth with alternative assembly | 51 mm |
|---|
Back to topAmbient conditions
| Degree of protection | IP20 |
|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested) |
|---|
| Ambient temperature (start-up type tested) | -40 °C |
|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
|---|
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
|---|
| Climatic class | 3K3 (in acc. with EN 60721) |
|---|
| Degree of pollution | 2 |
|---|
Back to topInput data
| Nominal input voltage range | 24 V DC |
|---|
| Input voltage range | 18 V DC ... 32 V DC |
|---|
| Current consumption | 14 A (24 V, IBOOST) |
|---|
| Inrush current | < 15 A (typical) |
|---|
| Mains buffering time | > 12 ms (24 V DC) |
|---|
| Input fuse | 25 A (internal (device protection)) |
|---|
| Choice of suitable circuit breakers | 16 A ... 20 A (Characteristics B, C, D, K) |
|---|
| Type of protection | Transient surge protection |
|---|
| Protective circuit/component | Varistor |
|---|
Back to topOutput data
| Nominal output voltage | 24 V DC ±1 % |
|---|
| Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
|---|
| Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
|---|
| POWER BOOST (IBoost) | 12.5 A (-25°C ... 40°C permanent, UOUT = 24 V DC ) |
|---|
| Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
|---|
| Derating | 60 °C ... 70 °C (2.5%/K) |
|---|
| Connection in parallel | Yes, for redundancy and increased capacity |
|---|
| Connection in series | yes |
|---|
| Feedback resistance | 35 V DC |
|---|
| Output overvoltage protection | < 35 V DC |
|---|
| Max. capacitive load | unlimited |
|---|
| Active current limitation | Approx. 18 A |
|---|
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
|---|
| < 2 % (change in load, dynamic 10 % ... 90 %) |
|---|
| < 0.1 % (change in input voltage ±10 %) |
|---|
| Residual ripple | < 20 mVPP |
|---|
| Peak switching voltages nominal load | < 10 mVPP (20 MHz) |
|---|
| Maximum power dissipation in no-load condition | 1.6 W |
|---|
| Power loss nominal load max. | 24 W |
|---|
Back to topGeneral
| Net weight | 0.9 kg |
|---|
| Efficiency | > 92 % |
|---|
| Insulation voltage input/output | 1.5 kV (type test) |
|---|
| 1 kV (routine test) |
|---|
| Protection class | III |
|---|
| Degree of protection | IP20 |
|---|
| MTBF (IEC 61709, SN 29500) | |
|---|
| > 763000 h (40 °C) |
|---|
| |
|---|
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
|---|
| Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
|---|